Model 6820 / 6820-EVS Installation Manual
11.8 Recording Custom Messages
The EVS-Series controls come with 15 recordable message slots. Message 1-15 can be recorded from the
microphone, Aux Input or by using the HFSS Honeywell Fire Software Suite message management utility. All
messages can be a maximum of one minute.
When in the record mode the EVS-VCM switches will function as follows:
Select Keys
1-15
While in the Local Record mode, select keys 1-15 will be used to reference message slots 1-15. The associated
green Select Key will indicate that a message is currently programmed in the corresponding slot. When there is
no message recorded (or the message is erased), the associated green Select Key LED will be off. While
recording a particular message, the red Select Key will turn on until recording is completed. The Select Key 1-15
will be used to playback a recorded message or to select a message slot to record to or erase.
When in the Local Record mode, the EVS-VCM LEDs will function as follows:
Switch LED
Select Key 1-15 Green LED
Select Key 1-15 Red LED
Select Key 1-15 Green/Red LED
Key
EVS Message Key 1
EVS Message Key 3
EVS Message Key 8
Select Keys 1-15
Table 11-1: LED Functions During Programming
Active LED Status
On
On
Off/Off
11-11
Function
Select message slot to record to
Start and stop recording from Aux Audio Input
Erase user message 1-15
Message slot 1-15
Meaning
Message is currently programmed in this slot
Message recording is in progress
Message slot is empty
LS10144-001SK-E
Message
Key 1
Message
Key 3
Message
Key 8

Advertisement