Advertisement

Operation
Silence Alarms and
Troubles
Reset alarms
View Alarms, Supervisories
and Troubles
View status of point
Conduct a fire drill
Check Detector Sensitivity
Set Time and Date
Enable / Disable a Point
View Event History
For Service Call:
6820 Basic Operating Instructions
These instructions must be framed and displayed next to the 6820 panel in accordance with
NFPA 72 fire code for Local Protected Fire Alarm Systems.
Press SILENCE then rotate the key or enter a code if prompted. Silence LED will light.
Press RESET then rotate the key or enter a code if prompted.
For each type of condition press the Up or Down button associated for Alarms, Supervisories, or Trou-
bles.
1. Press Enter to access the main menu.
2. Press 2 for Point Functions.
3. Select the module the device is located on by using the Up or Down button. Then press ENTER.
4. Enter the point number.
1. Press ENTER to access Main Menu.
2. Then Press 1 to select System Tests.
3. Press 1 to select Fire Drill.
4. Press ENTER to start the fire drill.
5. Press ENTER to end the fire drill.
1. Press ENTER to access Main Menu.
2. Press 2 for Point Status.
3. From the list that displays, select the SLC module where the point you want to view is located.
4. The fourth line of the display shows the sensitivity status.
"NORMAL" means the detector is in compliance with NFPA 72.
"CAL MAINT" means the detector is in compliance with NFPA 72 but maintenance should be per-
formed soon. "CAL TRBLE" means the detector is not in compliance with NFPA 72.
1. Press ENTER to access Main Menu.
2. Press 4 to select Set Time & Date. Enter a code if prompted
3. Make changes in the fields on the screen as necessary.
4. When the time and date are correct, press ENTER.
1. Press ENTER to access Main Menu.
2. Press 2 to select Point Functions.
3. Press 1 for Disable / Enable Pt
4. Press 7 for Disable / Enable Pt.
5. Use the Up or Down button to move through the list. Then press ENTER to select the module where
the point you want to disable/enable is located
6. Enter the point or circuit number that you want to disable/enable.
7. Press the right arrow key to toggle between NORMAL (enable) or DISABLE.
1. From the Program Menu.
2. Press 3 to select Event History.
3. Press the Up or Down button to view events in the history buffer.
Keystrokes
P/N: LS10160-001SK-E Rev. A
ECN 16-0218