Honeywell 6820EVS Installation And Optimization Manual page 22

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

Model 6820 / 6820-EVS Installation Manual
Model/Module
Description
Y = YES, N = NO, O = OPTIONAL
1. A maximum of eight 50/125 Watts Amplifiers for a maximum of 1000 Watts per EVS System.
2. A maximum of one Voice Control Module per EVS System.
3. A maximum of one Speaker Expander Module per Model EVS-50W/EVS-125W.
4. A maximum of two Remote Microphone modules per EVS System.
5. When configured for Emergency relocation and evacuation equipment the system must meet Local
configuration (Model 6820EVS) with a minimum of one amplifier (Model EVS-50W/EVS-125W or
EVS-INT50W) and one Voice Control Module (Model EVS-VCM).
NFPA Requirements for 6820EVS
Table 2-2:
CS
Local
Auxiliary
2-5
LS10144-001SK-E
Mass Notification
Remote
5
EVAC
Station
5
(In-Building)