Honeywell 6820EVS Installation And Optimization Manual page 229

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

Model 6820 / 6820-EVS Installation Manual
Smoke Detector/Base
System Sensor 1451 (w/B402B Base)
System Sensor 2112/24ATR
System Sensor 2112/24AITR
System Sensor 2112/24/D
System Sensor 2112/24R
System Sensor 2112/24TR
System Sensor 2112/24T/D
System Sensor 2112/24TSRB
System Sensor 2312/24TB
System Sensor 2412 (12 volt)
System Sensor 2412AT (12 volt)
System Sensor 2412TH (12 volt)
System Sensor 2424
System Sensor 2424TH
System Sensor 2451
System Sensor 2451TH (with/B402B
Base)
System Sensor 2W-MOD
System Sensor 4W-B (12/24 Volt)
System Sensor4WT-B (12/24 Volt)
System Sensor 4WTA-B (12/24 Volt)
System Sensor 4WTR-B (12/24 Volt)
System Sensor 4WTAR-B (12/24 Volt)
System Sensor 4WITAR-B (12/24 Volt)
System Sensor 2W-MOD2
System Sensor RRS-MOD
System Sensor 6424
System Sensor Beam 1224(S)
* Contact manufacturer for current draws
Detector Type
Ionization
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric w/135°
Thermal
Photoelectric w/135°
Thermal Supervisory Relay
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Loop Test/Maintenance
Mod.
3
Photoelectric I
3
Photoelectric I
w/Therm
3
I
Photo w/ Therm Sounder
3
I
Photo w/ Therm/Relay
3
I
Photo w/ Therm/
Sounder/Relay
3
I
Photo w/ Isolated Therm/
Sounder/Relay
3
I
Loop Test/Maintenance
Mod.
3
I
Reversing Relay/Sync
Module
Projected Beam
Projected Beam
11
LS10144-001SK-E
Max Standby
Alarm
Current (mA)
Current (mA)
0.10
39
0.50
60/70
0.50
60/70
0.05
50
0.50
60/70
0.50
60/70
0.05
50
15
45
0.12
50
0.12
77
0.12
58
0.12
77
0.10
41
0.10
41
0.10
39
0.10
39
30
50
.05
23
.05
23
.05
35
.05
35
.05
50
.05
50
.05
*
.05
*
10
28.4
17
38.5