Honeywell 6820EVS Installation And Optimization Manual page 245

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

ALL CALL
Key
Select
LED's
Select
Keys
LED
Color
Red
Select Keys
Green
EVS Control LED
Green
Red
EVS Message LED
Green
Integrated Voice Operation
Ready to
NON-ACTIVE CALL
Talk LED
Button
Table 1: LED Conditions
States
The corresponding area is active for the currently playing EVS
On
message.
Off
The corresponding area is not active.
On
The corresponding area is active for the microphone.
Off
The corresponding area is not active for the microphone.
LOC has EVS Control and the user is able to make changes to
On
the EVS.
Off
LOC does not have EVS Control.
Blinking
Another LOC has EVS Control
On
The corresponding EVS event was activated by an EVS device.
Off
The corresponding EVS event is not active.
The corresponding EVS event is active and was generated from
On
the LOC (or was activated from another LOC, but this LOC now
has EVS Control).
The corresponding EVS event was not activated from this LOC or
Off
this LOC does not have EVS Control.
EVS Control
Key
EVS Status LED
Message (1-8)
Activate Keys
Message
LEDS
Meaning
P/N: LS10161-001SK-E Rev A