Honeywell 6820EVS Installation And Optimization Manual page 147

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

LS10144-001SK-E
10. Repeat steps 1 through 9 for all circuits.
Table 9-5: Menu choices for Internal/External Power Module
Choices
Enter Point
UNUSED
B NOTIF
A NOTIF
AUX_PWR
B SWITCH
Select Type
A SWITCH
B DETECT
A DETECT
Function
Type Selections
Selections for
each Type
NOTIF Output
Control Circuit
CONSTANT
AUX RESET
AUX DOOR
Aux SYNC
MANUAL PULL
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
EVS INPUT
EVS TAMPER
EVS SUPERVISORY
Same as B SWITCH
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Aux Power for System Sensor
Refer to comments column of
Table 9-3 for description of these options.
Latch or Non-latching feature only appears for
WATERFLOW, FIRE SUPERVISORY, FIRE
TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM
AUX1, SYSTEM AUX2, EVS INPUT, EVS TAMPER,
and EVS SUPERVISORY.
User also has EVS Event Number 1-8 option for
EVS INPUT. Only available when an EVS-VCM is
installed in the system.
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class B, 4-wire CO detectors.
Latching or Non-latching used for Class B, 4-wire
CO Supervisory detectors
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Used for Class A, 4-wire CO detectors.
Latching or Non-latching used for Class A, 4-wire
CO Supervisory detectors
9-16
Programming
Comments