Underwriters Laboratories (Ul); Requirements For All Installations - Honeywell 6820EVS Installation And Optimization Manual

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

LS10144-001SK-E
qualified installer.
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1)
This device may not cause radio interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
Caution - To ensure proper operation, this equipment must be installed according to the enclosed installation
instructions. To verify that the equipment is operating properly and can successfully report an alarm, this
equipment must be tested immediately after installation, and periodically thereafter, according to the enclosed
test instructions.
Caution - In order for "alarm dialing equipment" to be able to seize the phone line to report an alarm or other
event when other customer equipment (telephone, answering system, computer modem, etc.) connected to the
same line is in use, "alarm dialing equipment" must be connected to a properly installed RJ31X jack. The RJ31X
jack must be connected in series with, and ahead of, all other equipment attached to the same phone line. Series
installation of an RJ31X jack is depicted in the figure below. If you have any questions concerning these
instructions, you should consult your telephone company or a qualified installer about installing the necessary
jack and alarm dialing equipment for you.
2.2

Underwriters Laboratories (UL)

2.2.1

Requirements for All Installations

General requirements are described in this section. When installing an individual device, refer to the specific
section of the manual for additional requirements. The following subsections list specific requirements for each
type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and
so on). See Section 10.7 for information on releasing operation.
1.
All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2.
Use the addressable smoke detectors specified in Section 7.2 (SD devices) or Section 7.1 (SK devices) of
this manual and/or conventional detectors listed in the compatibility chart. (See Appendix A).
3.
Use UL listed notification appliances compatible with the 6820 or 6820EVS from those specified in Appen-
dix A of this manual.
4.
A full system checkout must be performed any time the panel is programmed.
Restricted Options:
The loss of AC signal is defaulted to 3 hours, however the system allows settings from 0 - 30 hours. For UL
certified installations this number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in
commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding
applications, and hotel/motel room applications.
The system allows the Alarm Verification time to be set from 60 to 250 seconds. For UL certified
installations the setting must be a minimum of 60 seconds.
The systems allows the Auto-resound time to be set to 24 or 4 hours. For UL certified installations that are
utilizing SWIFT devices, the value must be set to 4 hours.
Call forwarding shall not be used.
When two count is used: detector spacing shall be cut in half, you shall not use the alarm verification feature,
and no delay shall be used.
P.A.S. (positive alarm sequence) feature shall be used only with automatic detectors.
Agency Listings, Approvals, and Requirements
Warning
2-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820

Table of Contents