Model 6820 / 6820-EVS Installation Manual
Type
Function
Selection
OUTPUT PT
AUX CONST
NOTIF
AUX RESET
AUX DOOR
OUTPUT PT
AUX RESET
RELAY
AUX DOOR
W-GATEWAY
W-SWITCH
Same as SWITCH
W-RELAY
Same as RELAY
9.5.3

Point Programming For Internal or External Power Module

To program for an internal or external power module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
4.
Press the up or down arrows to select the desired module. Refer to Section 9.5.3 for available choices, then
press ENTER.
5.
Enter the number of the circuit or point you wish to edit. Refer to Table 9-5 for available selections, then
press ENTER.
6.
Select the type by pressing the up or down arrows, then press ENTER.
7.
Select the function by pressing the up or down arrows, then press ENTER.
8.
Select the group by pressing the up or down arrows, then press ENTER.
9.
Edit point name. See Section Appendix B. Or, press the right arrow to skip point name edit.
Table 9-4 Point Programming for 6815
Latching Option
Output point, a general use notification type. Use for driving
Select Group
standard notification appliances.
Use constant power for applications that require a constant auxiliary
power source. Power is always present at constant circuits.
Use for auxiliary power, resettable applications. See Section 4.16.3
for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.16.3 for a description of how
this option operates.
Output point, a general use relay type. Use for applications requiring
Select Group
a relay, such as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See Section 4.16.3
for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.16.3 for a description of how
this option operates.
When a wireless relay is in use, module device count must be
limited to 109 modules per loop. This includes wired and wireless
modules that are on the same loop. The module address must be
within 1-109.
9-15
LS10144-001SK-E
Comments