Model 6820 / 6820-EVS Installation Manual
Section 9

Programming

This section of the manual describes how to manually program the control panel from the built-in annunciator.
Each subsection discusses these menu options in detail. All options described in this section can be performed
using HFSS Honeywell Fire Software Suite.
Before any customized programming is done, JumpStart
run, thoroughly test the system. The reason the system should be tested after JumpStart
®
JumpStart
automatically programs the system, searching for and configuring all SLC and SBUS
devices it finds. JumpStart allows you to confirm the integrity of the installation prior to performing
any custom programming. After determining that the hardware is properly installed, custom
programming can be performed.
9.1

UL 864 / UL 2572 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES: This product incorporates field programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 and UL 2572,
certain programming features or options must be limited to specific values or not used at all as indicated below.
Programming
Option
Time Options
Auto-resound
Time Options
Low AC Report Delay Yes
Display Oldest Event Y (Enabled)
N (Disabled)
Initial Delay
0-28
Inter Message Delay 4-32
Alarm Verification
Alarm Verification
Auto Reset EVS MIC
Auto Reset EVS MIC
Triggered Event
Triggered Event
EVS Input
EVS Input
Event Priority
CO Alarm
Important!
Permitted
in
Menu Item
UL 864
(Y/N)
Yes
Yes
No
Yes
No
Yes
Yes
Yes
No
®
should be run first. After JumpStart
Permitted
in
Possible
UL 2572
Settings
(Y/N)
Yes
4 hrs, 24hrs
Yes
0–30 hours
Yes
Yes & No
No
Yes & No
Yes
0-28
No
4-32
Yes
60-250
(confirmation
period)
Yes
Never
Timer Event
Disabled
Yes
Latching
Non-Latching
No
Yes & No
9-1
LS10144-001SK-E
®
is
®
is because
Settings
Settings
Permitted in
Permitted in
UL 864
UL 2572
4 hours if using
4 hours if using
SWIFT devices
SWIFT devices
1–3
1–3
Yes
Yes
No
No
3
3
4-32
4-28
60
60
Never
Never
Timer Event
Timer Event
Disabled
Disabled
Latching
Latching
No
No

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820

Table of Contents