6.5 Point Push Interface Definition
Point Push is an IEC 104 Server feature used to manually enter IEC 104 point data, date and time,
and/or flags information into the internal database of the EIS001 module. This feature is available in
either SOE mode, or NON-SOE Mode. It can be used to interface a Controller to an SOE or record-
based system (local or remote) so that records containing information from the source can be
transferred to the EIS001.
Point Push works by specifying a CPU memory interface region for the EIS001 to monitor. The
memory space specified is formatted with a custom record format that will be used by the EIS001 to
accept point push records.
6.5.1 Interface Specification
Set the value for the Point Push interface as required by the application.
Parameter
mComreq_Setup[68]
mComreq_Setup[69]
mComreq_Setup[70]
mComreq_Setup[71]
6.5.2 Record Format
The Point Push Record Format consists first of a 3-word Header Section and a 13-word Record
Section. The Record Section may be repeated up to eight times. Each iteration is concatenated to the
preceding Record Section.
Header Section of the Record Format
Index
[000]
[001]
[002]
Note: While the Point Push interface is operating, it continues to modify the header section. Note
that it takes multiple scans to accomplish a Point Push.
GFK-2949C
Chapter 6. Configuration of IEC 104 Server Parameters Using COMMREQ
Value
Description
0 / 1
0 = Disable Point Push
1 = Enable Point Push Using Controller memory
m-type
Memory Type for Point Push Table, Word
value
Value: 8-%R, 10-%AI, 12-%AQ, 196-%W, 0-unused
address
Memory Address Value for Point Push
value
1-Based, low word
for example, %R1 requires offset 1, %R100 requires offset 100
0
Memory Address Value
1-Based, high word
High word only used for accessing %W memory above 65535
Value
Description
1237
Specific value the EIS001 will look for to start the record
1 ... 65534 A counter or changed variable that will signal the EIS001 that
there is new data to be processed.
1 .. 8
Number of Record Sections to process
July 2017
55