Chapter 6. Configuration of IEC 104 Server Parameters Using COMMREQ

6.4 Optional Configuration Parameters

The parameters listed in Section 6.4 are optional for RX3i IEC 104 Server configuration files. The
optional parameters are application-based, or user-defined, configuration parameters that
determine the Server functionality and the responses to Client station requests. All configuration
parameter values should be entered in decimal format. Refer to the parameter description to
determine valid input values for application-based, or user-defined, parameter settings.
Note: Reserved parameters always have a value of zero (0).

6.4.1 Parameters for Filter Times

Parameter
mComreq_Setup[11]
mComreq_Setup[12]
Note: There is no interlock between the filter times.

6.4.2 Parameters for Short and Long Pulse Durations

Parameter
mComreq_Setup[13]
mComreq_Setup[14]
44
Value
Description
0 to 65530
Input Change Filter Time, default is 10 ms, typical [3x Controller
Sweep]. The Input Change Filter is a shutter on the data intake
by the module from the Controller.
If value configured is less than 10, then the value is internally
clamped to 10 ms by the EIS001 firmware.
If value configured is greater than 65530, then the value is
internally clamped to 65530 ms by the EIS001 firmware.
0 to 65530
Report By Exception Shutter Time, default is 25ms.
The RBE filter time is not a holding time. It is a general shutter
to control the flow of data back to the Client.
If value configured is less than 25, then the value is internally
clamped to 25 ms by the EIS001 firmware.
If value configured is greater than 65530, then the value is
internally clamped to 65530 ms by the EIS001 firmware.
Value
Description
0 to 65530
Short Pulse Duration, default 250 ms
Valid range 10 to 65530 ms.
If value configured is less than 10, then the value is internally
clamped to 150 ms by the EIS001 firmware.
If value configured is greater than 65530, then the value is
internally clamped to 65530 ms by the EIS001 firmware.
0 to 65530
Long Pulse Duration, default 500ms
Valid range 10 to 65530 ms.
If value configured is less than 10, then the value is internally
clamped to 500 ms by the EIS001 firmware.
If value configured is greater than 65530, then the value is
internally clamped to 65530 ms by the EIS001 firmware.
PACSystems RX3i Ethernet 104 Server Module User Manual
GFK-2949C