Chapter 2. Installation
2.3
Installation in Hazardous Areas
The following information is for products bearing the UL marking for Hazardous Areas or ATEX
marking for explosive atmospheres:
CLASS 1 DIVISION 2 GROUPS ABCD
•
This equipment is an open-type device and is meant to be installed in an enclosure suitable
for the environment that is only accessible with the use of a tool.
•
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or
nonhazardous locations only.
EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2.
WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR
WIRING MODULES; AND
DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.
2.3.1 ATEX Zone 2
The module must be mounted in an enclosure certified in accordance with EN60079-15 for use in
Zone 2, Group IIC and rated IP54. The enclosure shall only be able to be opened with the use of a tool.
2.3.2 ATEX Marking
II 3 G Ex nA IIC T5 X Ta: 0 - 60C
16
PACSystems RX3i Ethernet 104 Server Module User Manual
Warning
GFK-2949C