Appendix C Log Messages Table
All EIS001-specific faults are logged under Group 16. Other (ETM001-derived) module faults may also
be logged under Group 16. The EIS001 module faults are:
Module
Word 2 and 3
COMMREQ
16 # 10 10
Interpretation: The COMMREQ Sent by the Controller does not match the expected COMMREQ
length, and is too long.
COMMREQ
16# 10 10
Interpretation: The COMMREQ Sent by the Controller is a NULL.
MAIN
16# 00 00
Interpretation: General Message of the Firmware Revision, and module waiting for COMMREQ
MAIN
16# 00 01
Interpretation: General Message of the EIS001 Module starting after COMMREQ.
MAIN
16# 00 01
Interpretation: General Message the EIS001 Module has initialized and the MAIN loop is starting.
MAIN
16# FF FF
Interpretation: EIS001 Module has exited the main loop and shut down.
Demo
16# 00 0F
Interpretation: EIS001 Demo Mode has started, 4 hours of operation remains.
Startup
General Failure
Code
Interpretation: For GCC support of a Module that has a license but is failing to start as if licensed.
GFK-2949C
Word 4 and 5
Word 6 and 7
16 # 22 22
Length of
COMMREQ Sent
16# 22 22
16# FF FF
Revision 1
Revision 2
16# 00 01
16# 00 01
16# 00 01
16# 00 01
16# FF FF
16# FF FF
16# FF FF
16# FF FF
License a
License b Check
Check
July 2017
Word 8 and 9
Length of
COMMREQ
Expected
16# 00 01
16# 00 01
16# 00 01
16# 00 66
16# FF FF
16# FF FF
16# D6 E6
64