GE PACSystems RX3i User Manual page 84

Iec 104 server module ic695eis001
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

System information in control direction
(station-specific parameter, mark each Type ID 'X' if it is only used in the standard direction, 'R' if only
used in the reverse direction, and 'B' if used in both directions)
X
<100>:=
Interrogation command
<101>:=
Counter interrogation command
X
<102>:=
Read command
X
<103>:=
Clock synchronization command (option see 7.6)
X
<104>:=
Test command
<105>:=
Reset process command
<106>:=
Delay acquisition command
X
<107>:=
Test command with time tag CP56time2a
Parameter in control direction
(station-specific parameter, mark each Type ID 'X' if it is only used in the standard direction, 'R' if only
used in the reverse direction, and 'B' if used in both directions)
<110>:=
Parameter of measured value, normalized value
<111>:=
Parameter of measured value, scaled value
<112>:=
Parameter of measured value, short floating point value
<113>:=
Parameter activation
File Transfer
(station-specific parameter, mark each Type ID 'X' if it is only used in the standard direction, 'R' if only
used in the reverse direction, and 'B' if used in both directions)
<120>:=
File ready
<121>:=
Section ready
<122>:=
Call directory, select file, call file, call section
<123>:=
Last section, last segment
<124>:=
Ack file, ack section
<125>:=
Segment
<126>:=
Directory {blank or X, only available in monitor (standard) direction}
<127>:=
Query Log – Request archive file
GFK-2949C
July 2017
Appendix D. Device Profile
C_IC_NA_1
C_CI_NA_1
C_RD_NA_1
C_CS_NA_1
C_TS_NA_1
C_RP_NA_1
C_CD_NA_1
C_TS_TA_1
P_ME_NA_1
P_ME_NB_1
P_ME_NC_1
P_AC_NA_1
F_FR_NA_1
F_SR_NA_1
F_SC_NA_1
F_LS_NA_1
F_AF_NA_1
F_SG_NA_1
F_DR_TA_1
F_SC_NB_1
75