SPECIFICATIONS
The CPU module specifications are explained below.
2.1

Generic Specifications

Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
*5*6
Vibration resistance
*5
Shock resistance
Noise durability
Grounding
Working atmosphere
*8
Operating altitude
Installation location
*10
Overvoltage category
*11
Pollution degree
*1 The simultaneous ON ratio of available PLC inputs or outputs changes with respect to the ambient temperature, refer to Page 34
Input/Output Derating Curve.
*2 The operating ambient temperature is 0 to 55 for products manufactured before June 2016. For details on Intelligent function
modules, refer to manuals of each product.
*3 In the case where operating ambient temperature is lower than 0, the specifications are different from the above description. For
details, refer to Page 154 Precautions for Operating Ambient Temperature.
*4 When used in a low-temperature environment, use in an environment with no sudden temperature changes. If there are sudden
temperature changes because of opening/closing of the control panel or other reasons, condensation may occur, which may cause a
fire, fault, or malfunction. Furthermore, use an air conditioner in dehumidifier mode to prevent condensation.
*5 The criterion is shown in IEC61131-2.
*6 When the system has equipment which specification values are lower than above mentioned vibration resistance specification values,
the vibration resistance specification of the whole system is corresponding to the lower specification.
*7 For grounding, refer to Page 95 Grounding.
*8 The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
*9 The programmable controller is assumed to be installed in an environment equivalent to indoor.
*10 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises. Category  applies to equipment for which electrical power is supplied from
fixed facilities. The withstand surge voltage for the equipment with the rated voltage up to 300 V is 2500 V.
*11 This index indicates the degree to which conductive material is generated in the environment in which the equipment is used. Pollution
level 2 is when only non-conductive pollution occurs. Temporary conductivity caused by condensation must be expected occasionally.
Dielectric withstand voltage test and insulation resistance test
Perform dielectric withstand voltage test and insulation resistance test at the following voltages between each terminal and
the CPU module ground terminal.
■ CPU module, I/O module
Between terminals
Between power supply terminal (24 V DC) and ground terminal
Between input terminal (24 V DC) and ground terminal
Between output terminal (transistor) and ground terminal
Between output terminal (relay) and ground terminal
2 SPECIFICATIONS
30
2.1 Generic Specifications
Specifications
*1
*2*3
-20 to 55, non-freezing
-25 to 75, non-freezing
5 to 95%RH, non-condensation
5 to 95%RH, non-condensation
Frequency
Installed on DIN
5 to 8.4 Hz
rail
8.4 to 150 Hz
147 m/, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
By noise simulator at noise voltage of 1000 Vp-p, noise width of 1 s and period of 30 to 100 Hz
Class D grounding (grounding resistance: 100  or less) <Common grounding with a heavy electrical system is not
*7
allowed.>
Free from corrosive or flammable gas and excessive conductive dust
0 to 2000 m
*9
Inside a control panel
 or less
2 or less
*4
Acceleration
4.9 m/
Dielectric withstand voltage
500 V AC for one minute
1.5 kV AC for one minute
Half amplitude
Sweep count
1.75 mm
10 times each in X, Y, Z directions
(80 min in each direction)
Insulation resistance
10 M or higher by 500 V DC
insulation resistance tester
Remarks
I/O module only