Input matrix

Examples of wiring to take ON/OFF status of 24 switches by using MTR instructions are given below.
For the instructions, refer to MELSEC iQ-F FX5 Programming Manual (Instructions, Standard Functions/Function Blocks).
Programming examples
SM400
MTR
X10
Y10
Wiring examples
• Sink wiring
The example is the wiring for the input/output of the FX5UC-32MT/D.
Fuse
When the input
points X0 to X17
are used, connect
a pull-up resistor
(3.3 k/0.5 W).
FX5UC-32MT/D
• Source wiring
The example is the wiring for the input/output of the FX5UC-32MT/DSS.
Fuse
When the input
points X0 to X17
are used, connect a
pull-down resistor
(3.3 k/0.5 W).
FX5UC-32MT/DSS
*1 The grounding resistance should be 100  or less.
M30
K3
0.1 A 50 V
diode is
necessary.
24 V DC
Class D
*1
grounding
COM X10
COM0
COM0
0.1 A 50 V
diode is
necessary.
24 V DC
Class D
*1
grounding
COM0 X10
+V0
+V0
X11
X13
X15
X17
X12
X14
X16
X11
X13
X15
X17
X12
X14
X16
X11
X12
X13
X14
Sink input
Transistor output (sink)
Y10
Y11
Y12
Y13
Y14
X11
X13
X15
X17
X12
X14
X16
X11
X13
X15
X17
X12
X14
X16
X11
X12
X13
X14 X15
Source input
Transistor output (source)
Y10
Y11
Y12 Y13
Y14
6.7 Examples of Wiring for Various Uses
X15
X16
X17
Y15
Y16
Y17
X16
X17
Y15
Y16
Y17
6 WIRING