Limitation On The Number Of Input/Output Points; Total Number Of I/O Points And Remote I/O Points; Calculation Of The Number Of Input/Output Points - Mitsubishi Electric FX5UC-96MT/D User Manual

Melsec iq-f fx5uc series
Hide thumbs Also See for FX5UC-96MT/D:
Table of Contents

Advertisement

4.3

Limitation on the Number of Input/Output Points

With the FX5UC CPU modules, a total of 512 points including the number of input/output points of extension devices (max.
256 points) and the number of remote I/O points (max. 384 points) can be controlled.
Number of input/output points on whole system
1. Number of input/output points
(including input/output occupied points)
Expansion
adapter
2. Number of remote I/O points
CC-Link IE field network Basic system
Remote I/O station Remote I/O station
*1 A bus conversion module is required when using the FX3U-16CCL-M.
*2 A bus conversion module is required when using the FX3U-128ASL-M.

Total number of I/O points and remote I/O points

With the FX5UC CPU module, a total of 512 points or less including the number of input/output points of extension devices
and number of remote I/O points can be controlled.
The total number of I/O points and remote I/O points must not exceed 512 points.
Number of input/output
points on whole system
512 points
Maximum number of points
controllable on system

Calculation of the number of input/output points

The number of input/output points is a total of the number of input/output points of the CPU module, I/O module, and the
number of occupied input/output points of intelligent function modules.
The total number of input/output points must not exceed 256 points.
Maximum number of
input/output points
256 points
4 SYSTEM CONFIGURATION
58
4.3 Limitation on the Number of Input/Output Points
Connector
CPU
I/O
conversion
module
module
module
Number of input/output points
(1)
The total number of inputs and
outputs which is obtained in the
next subsection
Number of
input/output points
(1)
=
Total number of input/output points of CPU
module and I/O module
(A): Number of input/output points of CPU module (B): Number of input/output points of I/O module
(C): Number of intelligent function modules and bus conversion modules
Up to 512 points
Up to 256 points
FX5
FX5
• CC-Link master
Intelligent
Intelligent
• AnyWireASLINK master
module
module
Up to 384 points
CC-Link/AnyWireASLINK system
Remote I/O station Remote I/O station
points
+
Total number of remote I/O which is
obtained in the next subsection
Number of input/output points
on CPU module and I/O module
(A)
+
(B)
*1
*2
Number of remote I/O points
(2)
points
Number of occupied
input/output points
(C) modules  8 points
+
The intelligent module and bus
conversion module occupy 8
input/output points/device.