7.
Reboot the system.
Reboot the system by any of the following methods.
• Turning off and on the power
• Resetting the CPU module (Page 135 Resetting method)
8.
Check errors.
Check the ERR LED of the CPU module. If an error has occurred, check the contents of the error with Module Diagnostics
(CPU Diagnostics) of the engineering tool and eliminate its cause.
9.
Run the program.
Set the CPU module to the RUN status and make sure that the P.RUN LED of the CPU module lights up.
Connection with a personal computer
Connect the CPU module with a personal computer on which an engineering tool has been installed.
The system configuration examples and GX Works3 settings are described below.
For details, refer to GX Works3 Operating Manual.
Direct connection
Setting examples for accessing the CPU module that is directly connected with a personal computer are shown below.
■Ethernet connection
• Ethernet port direct connection
Ethernet port
1)
Ethernet cable
GX Works3 settings
No.
Item
1)
PC side I/F
2)
PLC side I/F
Other Station Setting
For the FX5 CPU module, the Ethernet adapter on the personal computer side used for the Ethernet port
direct connection can be specified. Click the [CPU Module Direct Coupled Setting] button on the "Specify
Connection Destination Connection" window to display the "CPU Module Direct Coupled Setting" window.
Select the adapter on the window.
• Connection via HUB
1)
GX Works3 settings
No.
Item
1)
PC side I/F
2)
PLC side I/F
Other Station Setting
Built-in
Ethernet
2)
Selection item
Internal setting
Ethernet Board
PLC Module
No Specification
Check at Communication Time
Retry Times
Built-in Ethernet
(192.168.0.2)
Hub
2)
Selection item
Internal setting
Ethernet Board
PLC Module
Connection via HUB
No Specification
Check at Communication Time
Retry Times
Input value
Ethernet Port Direct Connection
30 seconds
0 times
Input value
IP Address
192.168.0.2
Response Waiting Time
2 seconds
30 seconds
0 times
7 OPERATION ADJUSTMENT
7.1 Preparation for Operation
7
133