Advertisement

4DI NAMUR
No sensor supply
Diagnostics: wire break
Diagnostics: wire break
Chatter monitoring:
Monitoring window
1
Chatter monitoring:
Number of signal changes
The parameters can only be set when the number of signal changes for chatter monitoring is activated
1
3.1.3

Parameters for digital output modules

This table shows the parameters for digital output modules:
Table 3-3
Parameters for digital output modules
2DO 24
2DO
VDC/0.5 A
24 VAC to
High Feature
230 VAC/1 A
2DO 24
2RO NO
VDC/2 A
24 VDC to
High Feature
120 VDC/5 A
24 VAC to
230 VAC/5 A
Reaction to CPU-/master-STOP
Substitute value
1
Diagnostics:
Wire break
2
Diagnostics:
Short-circuit
to M
If the interface module or COMPACT module becomes deenergized, the digital output modules will not produce
1
substitute values.
Output value = 0.
A wire break is only detected in the switched output state.
2
ET 200S
Manual, Edition 10/2005, A5E00514527-01
Range of values
disable
Enable
disable
Enable
disable
0.5 s
1 s to 100 s (can be set
at increments of 1 s)
disable
2 to 31
2RO NO NC
24-48 VDC/5 A 24-
230 VAC/ 5 A
---
---
3.1 Parameters for digital electronic modules
Default setting
disable
disable
0.5 s
disable
2DO/ 4DO 24
Range of values
VDC/0.5 A
Standard
2DO/ 4DO 24
VDC/2 A
Standard
Substitute a
---
value
Keep last
value
"0"
---
"1"
disable
Enable
disable
Enable
Digital electronic modules
Applicability
Channel
Channel
Channel
Channel
Default
Applicability
setting
Substitute a
Module
value
"0"
Channel
disable
Channel
disable
Channel
3-3