Galvanic isolation
•
•
Permissible potential difference
•
Insulation tested
Current consumption
•
Power dissipation of the module
Status display
Diagnostics function
Output voltage
•
Output current
•
•
Output delay (for resistive load)
•
•
Load resistor range
Lamp load
Connecting two outputs in parallel
•
•
Control of a digital input
Switch rate
•
•
•
Limitation (internal) of the voltage induced on
circuit interruption
Reverse-voltage proof
Short-circuit protection of the output
•
Polarity reversal can lead to the digital outputs being connected through.
1
Per channel
2
ET 200S
Manual, Edition 10/2005, A5E00514527-01
3.12 2DO 24 VDC/0.5 A Standard digital electronic module (6ES7132-4BB01-0AA0)
Between the channels
Between the channels and backplane bus
Between the different circuits
From the load voltage L+ (no load)
At signal "1"
At signal "1"
Rated value
–
Permitted range
–
With signal "0" (leakage current)
at "0" to "1"
At "1" to "0"
For redundant triggering of a load
To increase performance
For resistive load
On inductive load
For lamp load
Threshold on
no
Yes
75 VDC / 60 VAC
500 VDC
max. 5 mA per channel
Typically 0.4 W
Status, interrupts, diagnostics
Green LED per channel
no
Data for selecting an actuator
min. L+ (-1 V)
0.5 A
7 mA to 0.6 A
max. 0.3 mA
max. 200 µs
max. 1.3 ms
48 Ω to 3.4 kΩ
max. 5 W
Yes (per module)
no
Yes
100 Hz
2 Hz
10 Hz
Typically L+ (-55 to -60 V)
Yes, if using the same load voltage as at the
power module
Yes
2
Typ. 0.7 A to 1.8 A
Digital electronic modules
3-51