Siemens Simantic ET 200S Manual page 95

Distributed i/o system
Table of Contents

Advertisement

Galvanic isolation
Permissible potential difference
Insulation tested
Current consumption
Power dissipation of the module
Status display
Diagnostics function
Output voltage
Output current
Output delay (for resistive load)
Load resistor range
Lamp load
Connecting two outputs in parallel
Control of a digital input
Switch rate
Limitation (internal) of the voltage induced on
circuit interruption
Reverse-voltage proof
Short-circuit protection of the output
Polarity reversal can lead to the digital outputs being connected through.
1
Per channel
2
ET 200S
Manual, Edition 10/2005, A5E00514527-01
3.12 2DO 24 VDC/0.5 A Standard digital electronic module (6ES7132-4BB01-0AA0)
Between the channels
Between the channels and backplane bus
Between the different circuits
From the load voltage L+ (no load)
At signal "1"
At signal "1"
Rated value
Permitted range
With signal "0" (leakage current)
at "0" to "1"
At "1" to "0"
For redundant triggering of a load
To increase performance
For resistive load
On inductive load
For lamp load
Threshold on
no
Yes
75 VDC / 60 VAC
500 VDC
max. 5 mA per channel
Typically 0.4 W
Status, interrupts, diagnostics
Green LED per channel
no
Data for selecting an actuator
min. L+ (-1 V)
0.5 A
7 mA to 0.6 A
max. 0.3 mA
max. 200 µs
max. 1.3 ms
48 Ω to 3.4 kΩ
max. 5 W
Yes (per module)
no
Yes
100 Hz
2 Hz
10 Hz
Typically L+ (-55 to -60 V)
Yes, if using the same load voltage as at the
power module
Yes
2
Typ. 0.7 A to 1.8 A
Digital electronic modules
3-51