Parameters For 2Ai Rtd High Feature Analog Electronic Module - Siemens Simantic ET 200S Manual

Distributed i/o system
Table of Contents

Advertisement

Analog electronic modules
4.5 Parameters for analog electronic modules
2AI RTD
2AI TC Standard
Standard
Only with thermocouples. A parameter assignment error occurs when the wire break diagnosis is enabled in the voltage
1
measuring range. The module does not start up.
The wire break is only detected with constant-current lines.
2
See also
Connecting Thermocouples (Page 4-18)
4.5.5

Parameters for 2AI RTD High Feature analog electronic module

Table 4-34
Parameters for 2AI RTD High Feature analog electronic module
Parameters
Group diagnostics
Diagnostics:
overflow/underflow
Diagnostics: Wire break
Smoothing
Temperature unit
Type of measurement
4-30
2AI TC High
Feature
Type/range of
measurement
Range of values
Disable
Enable
Disable
Enable
Disable
1
Enable
None
Weak
Medium
Strong
Celsius
Fahrenheit
De-activated
Four-wire resistor
Three-wire resistor
Two-wire resistor
Four-wire thermal resistor
Three-wire thermal resistor
Two-wire thermal resistor
Range of values
De-activated
Voltage ± 80 mV
TC-EL type T (Cu-CuNi)
TC-EL type K (NiCr-Ni)
TC-EL type B (PtRh-PtRh)
TC-EL type C (WRe-WRe)
TC-EL type N (NiCrSi-NiSi)
TC-EL type E (NiCr-CuNi)
TC-EL type R (PtRh-Pt)
TC-EL type S (PtRh-Pt)
TC-EL type J (Fe-Cu-Ni)
TC-EL type L (Fe-Cu-Ni)
Default setting
Disable
Disable
Disable
None
Celsius
Four-wire thermal
resistor
Default setting
Applicability
TC-EL type K
Channel
(NiCr-Ni)
Applicability
Module
Module
Channel
Channel
Module
Channel
Manual, Edition 10/2005, A5E00514527-01
ET 200S

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents