Measuring principle
Integration time/conversion time/resolution
per channel:
Interference voltage suppression for
f = n x (f1 ± 1 %), (f1 = interference
frequency)
Crosstalk between the inputs
Operational limit for ±80 mV (over the entire
temperature range with reference to the
input range)
Operational limit for thermocouples (over
the entire temperature range with reference
to the input range)
Operational limit for thermocouple type C (in
the entire temperature range with reference
to the input range)
Basic error limit for ±80 mV (operational
limit at 25 °C with reference to the input
range)
Basic error limit for thermocouples
(operational limit at 25 °C with reference to
input range)
Basic error limit for thermocouples of type C
(operational limit at 25 °C with reference to
the input range)
Temperature error (with reference to the
input range)
Linearity error (with reference to the input
range)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4.18 2AI RTD High Feature analog electronic module (6ES7134-4NB01-0AB0)
Integration time can be assigned
parameters
Interference frequency suppression in
Hz
Integration time in milliseconds
Basic conversion time incl. integration
time in ms
Additional conversion time for wire break
check diagnosis in ms
Cycle time in ms
Resolution (including overrange)
Common-mode interference (U
Series-mode interference
(peak interference value < rated value of
input range)
1
1
1
1
Analog value generation
Integrative
Yes
60
16.7
66
5
Number of active channels per module x conversion
time
15 bits plus sign
Suppression of interference, limits of error
)
min. 90 dB
SS
min. 70 dB
min. -50 dB
± 0.1 %
± 1.5 K
± 7 K
± 0.05 %
± 1 K
± 5 K
± 0.005 %/K
± 0.01 %
Analog electronic modules
50
20
80
5
4-93