4.20 2AO U High Feature analog electronic module (6ES7135-4LB02-0AB0)
Crosstalk between the outputs
Operational limit
(in the entire temperature range, with
reference to the output range)
Basic error limit (operational limit at 25 °C with
reference to output range)
Temperature error (with reference to the
output range)
Linearity error (with reference to the output
range)
Repeatability (in steady state at 25 °C with
reference to output range)
Output ripple; range 0 Hz to 50 kHz (relative to
output range)
Output range (rated value)
Load impedance (in the rated range of the
output)
Voltage output
Destruction limit against voltages/currents
applied from outside
Connection of actuators
4-102
At voltage outputs
Capacitive load
Short-circuit protection
Short-circuit voltage
Voltage at the outputs to M
Current
Voltage output
2-wire connection
4-wire connection
Suppression of interference, limits of error
> 60 dB
± 0.07 %
± 0.03 %
± 0.001 %/K
± 0.02 %
± 0.01 %
± 0.02 %
Data for selecting an actuator
± 10 V
1 V to 5 V
min. 1.0 kΩ
max. 1 µF
yes
approx. 25 mA
max. 15 V continuous; 75 V for max. 1 ms
ANA
(sampling ratio 1:20)
max. 50 mA DC
Possible, without compensation of the line
resistances
Possible
Manual, Edition 10/2005, A5E00514527-01