Siemens Simantic ET 200S Manual page 169

Distributed i/o system
Table of Contents

Advertisement

2AI U Standard Technical Specifications (6ES7134-4FB01-0AB0)
Dimensions W × H × D (mm)
(the total dimensions depend on the selected
terminal module)
Weight
Supports isochronous operation
Number of inputs
Cable length
Parameter length
Rated load voltage L+ (from the power
module)
Galvanic isolation
Permissible potential difference
Insulation tested
Current consumption
Power dissipation of the module
Diagnostics function
Measuring principle
Integration and cycle time/resolution per
channel:
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4.6 2AI U Standard analog electronic module (6ES7134-4FB01-0AB0)
Shielded
Reverse polarity protection
Between the channels and backplane bus
Between the channels and load voltage L+
Between the channels
Between the inputs and M
Between M
and the central grounding
ANA
point (U
)
ISO
From load voltage L+
Group error
Diagnostic functions readable
Integration time can be assigned
parameters
Interference frequency suppression in Hz
Integration time in milliseconds
Conversion time in ms
Cycle time in ms
Resolution (including overrange)
Dimensions and Weight
15 x 81 x 52
Approx. 40 g
Data for specific modules
no
2
max. 200 m
4 bytes
Voltages, currents, potentials
24 VDC
Yes
Yes
Yes
no
(U
)
2 VAC
ANA
CM
75 VDC / 60 VAC
500 VDC
max. 30 mA
Typically 0.6 W
Status, interrupts, diagnostics
Red "SF" LED
Yes
Analog value generation
Integrative
Yes
60
16.7
55
Number of active channels per module x conversion
time
± 10 V/13 bits + sign
± 5 V/13 bits + sign
1 V to 5 V/13 bits
Analog electronic modules
SS
50
20
65
4-39

Hide quick links:

Advertisement

Table of Contents
loading