Digital Output Modules (TXM1.6R and TXM1.6R-M)

18
Siemens Industry, Inc.
588-587
Digital Input Grounding Connections
The neutral of a digital input (on Digital Input, Universal and Super Universal modules)
can be connected to any neutral terminal on the same module. Several digital inputs
can also share a neutral terminal on the same module.
Technical Data
Digital inputs are not electrically separated from the system electronics.
Mechanical contacts must be volt-free.
Contact sensing voltage
Contact sensing current
Contact resistance with contacts closed
Insulation resistance with contacts open
Min. closing / opening
time [ms] including
bouncing
Maintained contact
80
Pulse contact
50
Counter
40
1)
Counting function for TXM1.16D is on I/O points 1 through 8 only.
1)
20
26
19
21
25
27
(4)
(5)
24V ...250V
(1)
(2)
(3)
(4)
(5)
(1)
(2)
2
4
8
10
3
9
The TXM1.6R and TXM1.6R-M Digital Output modules provide six NO or NC (form C),
maintained or pulsed, voltage free/dry contacts.
CONFIDENTIAL: For internal use only
21.5 to 25 Vdc
1.6 mA (initial current 10 mA)
Max. 200Ω
Max. 50KΩ
Max. bounce time
[ms]
40
30
30
32
31
33
19
(6)
TXM1.6R
(6)
(3)
14
16
15
TALON TX-I/O Modules and Island Bus Technical Reference
Max. Counting
frequency
(symmetric)
10 Hz
20
26
32
21
25
27
31
33
(4)
(5)
(6)
TXM1.6R-M
24V ...250V
(1)
(2)
(3)
(4)
(5)
(6)
+
(1)
(2)
(3)
2
4
8
10
14
16
3
9
15
4/6/2010