Analog electronic modules
4.19 2AO U Standard analog electronic module (6ES7135-4FB01-0AB0)
Diagnostics function
•
•
Resolution (including overrange)
Cycle time
Settling time
•
•
•
Substitute value can be assigned parameters
Crosstalk between the outputs
Operational limit (in the entire temperature
range, with reference to the output range)
Basic error limit (operational limit at 25 °C with
reference to output range)
Temperature error (with reference to the
output range)
Linearity error (with reference to the output
range)
Repeatability
(in steady state at 25 °C with reference to
output range)
Output ripple (with reference to output range,
bandwidth 0 to 50 kHz)
Data for selecting an actuator
Output range (rated value)
Load resistance
•
•
•
Destruction limit against voltages/currents
applied from outside
•
•
Connection of actuators
•
•
4-98
Group error
Diagnostic functions readable
For resistive load
For capacitive load
For inductive load
For capacitive load
Short-circuit protection
Short-circuit voltage
Voltage at the outputs to M
Current
Two-wire connection
Four-wire connection
Status, interrupts, diagnostics
Red "SF" LED
Yes
Analog value generation
± 10 V/13 bits + sign
1 to 5 V/12 bits
max. 1.5 ms
0.1 ms
0.5 ms
0.5 ms
Yes
Suppression of interference, limits of error
min. -40 dB
± 0.4 %
± 0.2 %
± 0.01 %/K
± 0.02 %
± 0.05 %
± 0.02 %
± 10 V
1 V to 5 V
min. 1.0 kΩ
max. 1 µF
Yes
Approx. 25 mA
15 V continuous; 75 V for max. 1 ms
ANA
(sampling ratio 1:20)
max. 50 mA DC
Possible, without compensation of cable resistance
Yes
Manual, Edition 10/2005, A5E00514527-01
ET 200S