Siemens Simantic ET 200S Manual page 124

Distributed i/o system
Table of Contents

Advertisement

Digital electronic modules
3.19 2RO NO 24 VDC to 120 VDC/5 A, 24 VDC to 230 VAC/5 A digital electronic module (6ES7132-4HB01-
0AB0)
Galvanic isolation
Permissible potential difference
Insulation tested
Current consumption
Power dissipation of the module
Status display
Diagnostics function
Output current
Connecting two outputs in parallel
Control of a digital input
Switch rate
Limitation (internal) of the voltage induced on
circuit interruption
Short-circuit protection of the output
The relay outputs must be fused externally with 6 A.
1
3-80
Between the channels
Between the channels and backplane bus
Between the channels and supply voltage
Between the supply voltage and backplane
bus
Between the supply voltage and backplane
bus
Between channels and backplane bus
Between the channels and supply voltage
Between the supply voltage and backplane
bus
Between channels and backplane bus
Between the channels and supply voltage
From the power supply L+
Continuous thermal current
Min. load current
min. voltage
For redundant triggering of a load
To increase performance
For resistive load
On inductive load
For lamp load
Yes
Yes
Yes
Yes
75 VDC / 60 VAC
240 VAC
240 VAC
Yes
500 VDC
1500 VAC
1500 VAC
max. 30 mA
Typically 0.6 W
Status, interrupts, diagnostics
Green LED per channel
no
Data for selecting an actuator
max. 5 A
8 mA
17 V
no
no
Yes
2 Hz
0.5 Hz
2 Hz
no
no
1
Manual, Edition 10/2005, A5E00514527-01