Siemens Simantic ET 200S Manual page 186

Distributed i/o system
Table of Contents

Advertisement

Analog electronic modules
4.10 4AI I 2WIRE Standard analog electronic module (6ES7134-4GD00-0AB0)
Interference voltage suppression for f = n x (f1
± 1%), (f1 = interference frequency)
Crosstalk between the inputs
Operational limit
(in the entire temperature range, with reference
to the input range)
Basic error limit (operational limit at 25° C with
reference to input range)
Temperature error (with reference to the input
range)
Linearity error (with reference to the input range)
Repeatability
(in steady state at 25° C with reference to input
range)
Input range (rated value)/input resistance
Permitted input current (destruction limit)
Load of the two-wire measuring transducer
Smoothing of the measured values
4-56
Common mode interference
(peak value of interference < rated value of
input range)
Current
Suppression of interference, limits of error
min. 70 dB
min. -50 dB
± 0.4%
± 0.3%
± 0.003 %/K
± 0.01%
± 0.05%
Data for selecting a sensor
4 mA to 20 mA/25 Ω
Approx. 30 mA (limited electronically)
max. 750 Ω
Yes, can be assigned parameters in 4 steps
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
16 x cycle time
32 x cycle time
Manual, Edition 10/2005, A5E00514527-01