Emerson Rosemount 8800D Series Reference Manual page 114

Vortex flowmeter
Hide thumbs Also See for Rosemount 8800D Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4004, Rev DC
Table A-6. Water Flow Rate Limits for the Rosemount 8800D and 8800DR
Process line size
(Inches/ DN)
0.5/ 15
1/ 25
1.5/ 40
2/ 50
3/ 80
4/ 100
6/ 150
8/ 200
10/ 250
12/ 300
1.
Table A-6
is a reference of flow rates that can be measured for the standard Rosemount 8800D and the reducer 8800DR Vortex Meters. It does
not consider density limitations, as described in
2.
Velocity range of the 8800DW is the same as 8800DF.
3.
Conditions: 77 °F (25 °C) and 14.7 psia (1.01 bar absolute)
106
Minimum and maximum measurable water flow rates
(2)
Vortex meter
8800DF005
8800DF010
8800DR010
8800DF015
8800DR015
8800DF020
8800DR020
8800DF030
8800DR030
8800DF040
8800DR040
8800DF060
8800DR060
8800DF080
8800DR080
8800DF100
8800DR100
8800DF120
8800DR120
Table A-2
and
Table
Specifications and Reference Data
Gallons/minute
1.76 to 23.7
2.96 to 67.3
1.76 to 23.7
4.83 to 158
2.96 to 67.3
7.96 to 261
4.83 to 158.0
17.5 to 576
7.96 to 261.0
30.2 to 992
17.5 to 576
68.5 to 2251
30.2 to 992
119 to 3898
68.5 to 2251
231 to 6144
119 to 3898
391 to 8813
231 to 6144
A-3.
May 2016
(1)
Cubic meters/hour
0.40 to 5.4
0.67 to 15.3
0.40 to 5.4
1.10 to 35.9
0.67 to 15.3
1.81 to 59.4
1.10 to 35.9
4.00 to 130
1.81 to 59.3
6.86 to 225
4.00 to 130
15.6 to 511
6.86 to 225
27.0 to 885
15.6 to 511
52.2 to 1395
27.0 to 885
88.8 to 2002
52.2 to 1395
Specifications and Reference Data
(3)