Emerson Rosemount 8800D Series Reference Manual page 108

Vortex flowmeter
Hide thumbs Also See for Rosemount 8800D Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4004, Rev DC
Storage
–58 to 250 °F (–50 to 121 °C)
–50 to 185 °F (–46 to 85 °C) for flowmeters with local indicator
Pressure limits
Flange style meter
Rated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and 1500, EN 1092-1, PN 10, 16, 25,
40, 63, 100, and 160, and JIS 10K, 20K, and 40K
Reducer style meter
Rated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and 1500, EN 1092-1, PN 10, 16, 25,
40, 63, 100, and 160.
Dual sensor style meter
Rated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and 1500, EN 1092-1, PN 10, 16, 25,
40, 63, 100, and 160, and JIS 10K, 20K, and 40K
Wafer style meter
Rated for ASME B16.5 (ANSI) Class 150, 300, and 600, EN 1092-1, PN 10, 16, 25, 40, 63, and
100, and JIS 10K, 20K, and 40K
Note
All Wafer Style Meters are pressure rated and labeled at 1500 PSI/10.34 MPa at 100 °F/38 °C
regardless of Alignment Ring Size code ordered.
Weld-end style meter
W1 Welds to Schedule 10 mating pipe
Max Working Pressure 720 psig (4.96 MPa-g)
W4 Welds to Schedule 40 mating pipe
Max Working Pressure 1440 psig (9.93 MPa-g)
W8 Welds to Schedule 80 mating pipe
Max Working Pressure 2160 psig (14.9 MPa-g)
W9 Welds to Schedule 160 mating pipe
Max Working Pressure 3600 psig (24.8 MPa-g)
Note
1-in. (25 mm), and 1.5-in. (40 mm) weld to Schedule 80 mating pipe
HART analog
External power supply required. Flowmeter operates on 10.8 to 42 Vdc terminal voltage
(with 250Ω minimum load required for HART communications, 16.8 Vdc power supply is
required)
100
Specifications and Reference Data
Specifications and Reference Data
May 2016