Parameter 35 "Stepping end CLOSED in per mil"
End stepping range in direction CLOSE with indication of position in per mil.
This value must be higher than the value in parameter 34 (stepping start
CLOSE in per mil). This parameter is only effective if parameter 31 (stepping
direction CLOSE active) is not 0. Otherwise, the total parameter record will
be rejected.
Holding Register Offset: 0x4022 (hexadecimal), 16418 (decimal)
Default value: 0
minimum value: 0 (stepping mode in direction CLOSE ends at position 0,
end position CLOSED)
maximum value: 999
Parameters 36 to 50 are spare parameters
They are reserved for extensions.
Default value: 0
Value range: 0 to 65535