System Controller Specifications; Static Switch (St/Sw) Module; Table 2-2: System Controller Specifications - Gamatronic POWER PLUS Technical Manual

Modular ups system 10 kva to 100 kva, 3x400 v
Table of Contents

Advertisement

2.2.1

SYSTEM CONTROLLER SPECIFICATIONS

Micro Controller core
Display
Other indicators
Analog input channels
Digital input channels
Real Time Clock (RTC)
Power meter
Voltage-free outputs (dry contacts)
RS232 user port
Optional communication
Communications with system modules
Events log
System operation without controller
On-screen parameters
Alarms
RTC operation without power
Power requirements
2.3

STATIC SWITCH (ST/SW) MODULE

The static switch module is used for overriding the input to output in case of a system failure or
heavy load start or if specifically requested by the user.
The module receives two AC inputs and supplies only one.
Generally the ST/SW connects the output of the paralleled UPS modules to the main output of
the system. However, if the modules fail to provide an adequate voltage for a determined time,
i.e. detection time, the ST/SW module instantly switches to the alternative power source, that is
the AC input, as illustrated in Figure 2-10. The unit employs an efficient AC switch for this
purpose using a combination of fast semiconductors and an electromechanical relay.
The module monitors all the inputs in real time to determine the method of operation. The
ST/SW module's front panel is shown in Figure 2-9.
12

Table 2-2: System controller specifications

TECHNICAL DATA – SYSTEM CONTROLLER
Gamatronic Electronic Industries Ltd.
16 bit
4 x 40 characters LCD with backlight
8 LED's, buzzer
4
8
Yes, with backup
kVA, kW, PF
6
Yes, isolated
TCP/IP, GPRS/SMS Wireless
communication (Optional)
Serial, isolated
255 events
Unchanged
Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
AC abnormal
DC abnormal
UPS module(s) failure
Load on bypass
Battery test failed
Over/under temperature
Overload
2 weeks
12V±10%, 1A via 2.1mm phono jack
Power+ Technical Guide

Advertisement

Table of Contents
loading

Table of Contents