11. SETUP PROCEDURES
The options in the Setup Menu enable you to configure system parameters.
Option
1 ALARM SET
2 UPS
3 BATTERY
4 CHARGE
5 TIME
6 SITE
7 PASSWORD
8 SERVICE
9 SILICON
11.1
SETTING ALARM THRESHOLDS
It is possible to define the threshold values for setting off alarms for the parameters of system
components. An alarm is set off each time a parameter value is outside the defined range of
permitted values.
Press the number that appears beside a menu option to open a screen in which you can set the
alarm thresholds for that option.
O
PTION
0 AC VOLT
1 OUTPUT VOLT
6 BATTERY
7 TEMPERATURE
8 VIBRATION
9 INTEGRATION
Power+ Technical Guide
Table 11-1: Setup Menu options
Description
Opens menu with options for setting the threshold levels that
trigger alarms
Sets the UPS Parameters
Sets the Battery current parameters
Sets the Charge mode parameters
Sets the systems clock which sets a time stamp on log entries
Sets the power system's ID number
Sets Level 1 Password
Opens menu of service utility programs
Opens menu with options for restoring factory-defined default
values to parameters
Table 11-2: Setting alarm thresholds
D
ESCRIPTION
Sets the permitted AC voltage range (minimum and maximum input
voltage) and the AC voltage hysteresis
Sets the permitted DC voltage range (minimum and maximum
output voltage)
Sets the permitted battery voltage range (minimum and maximum
output voltage) (indicates possible battery fault)
Sets the permitted battery temperature range (minimum and
maximum temperature)
Sets the number of times an alarm must occur within a specified
period of time to be considered a vibrating alarm
Sets the number of times the controller must receive an alarm from
the system before it logs the alarm
85