3.9.6.2
Q: W
ARE ALWAYS ON
A. There is a number of alarms that might be on. One of them is the "STRTUP" alarm, which stands for
the "startup time stamp". This alarm only means that the unit is on, and it will not raise an "alarm signal".
Other alarms can be the "user alarm 1-4", which are the input dry contacts. If they are not in use, you
can disable them through the controller menus.
3.9.6.3
Q: W
A. The equalizing mode should always be set to DISABLED, this feature is not available. If you had it on
in your system, please note that it could simulate a failure condition and a shutdown to the computers.
On all the units today this feature is absent. Please contact your Gamatronic representative to upgrade
your controller software version.
3.9.6.4
Q: T
HE UNIT ALWAYS SHOWS BATTERY TEST FAULT ALARM
OK. W
ARE
A. On some older systems the controller might show false battery alarms. This was corrected, so in case
that you have this problem and positively sure that the batteries are alright, please contact your
Gamatronic representative to upgrade your controller software version. After you perform this action, the
unit will still show battery test fault. Please perform manual battery test to restore normal operation.
44
I
HEN
LOOK AT THE LIST OF THE ALARMS
. W
HY IS THAT
HAT WILL HAPPEN IF THE EQUALIZING MODE WAS ACTIVATED IN THE UNIT
HAT IS WRONG
Gamatronic Electronic Industries Ltd.
, I
?
?
CAN SEE SOME ALARMS WHICH
. T
HE BATTERIES
Power+ Technical Guide
?