Table 5-3: Log Messages "Description" Field - Gamatronic POWER PLUS Technical Manual

Modular ups system 10 kva to 100 kva, 3x400 v
Table of Contents

Advertisement

Gamatronic Electronic Industries Ltd.
Alarm
Message
#
01
UPSMAJ
02
UPSMIN
03
------
04
------
05
LOADBP
06
VIBRA_
07
OVTEMP
08
OUTFLT
09
BAT-HI
10
------
11
BATEND
12
BATLOW
13
STSWRN
14
E.P.O.
15
EQ-HST
16
BATFLT
17
USER-1
18
USER-2
19
USER-3
20
AC-BRN
21
ACIN_H
22
ACFAIL
23
STSWCM
24
SLFFLT
25
BAT-CB
26
CURSHR
27
UPSOUT
28
UPSHDN
29
OVLOAD
30
UPS-CM
31
STRTUP
32
------
Power+ Technical Guide
Table 5-3
: Log Messages "description" field
Explanation
More than 1 UPS Module is sending an alarm or fault warning.
Single UPS Module is sending an alarm or fault warning.
N.A.
N.A.
Load is now running on bypass. "Data" field holds the STSW transfer
code – see Table 5-4 for interpretation of the STSW transfer code.
Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to avoid
loading the log filling up.
Excess temperature.
No ac output to load.
Excessive battery voltage.
N.A.
End of battery backup. Battery is discharged to shutdown limit.
Low battery voltage.
Static Switch Warning or alarm.
Emergency Power Off is active.
Battery is currently charging in equalizing mode, dc voltage is temporarily
increased.
Batteries failed last test.
User 1 input open.
User 2 input open
User 3 input open.
Input ac supply brown-out.
Ac input excessive.
Ac input failure.
Static Switch does not respond.
Last controller self-test failed.
Battery circuit breaker open.
Current Sharing fault, load current is not equally divided between
modules.
Fault (no current) in 1 or more output stage.
UPS shutdown by EPO, Battery Discharge, ON/OFF pressed.
Load current is high.
One or more UPS's not responding.
Startup time-stamp.
N.A.