3.3

AC INPUT FUSES

The input of each UPS module is protected by a 15A fuse for each phase, so that each module,
including the controller, has 3 fuses (for R, S, T phases). 10 modules plus the controller would
require 33 fuses, as illustrated in Figure 3-15. Fuse receptacles are numbered from right to left,
i.e. the 3 fuses on the far right protect UPS #1.

Figure 3-15: UPS modules - AC input fuses (100KVA model)

WARNING
ALWAYS REPLACE FUSES WITH THE SAME TYPE AND RATINGS !!!

Figure 3-16: AC input fuse assignments (50KVA model)