Interface assignment of X122, X132 and X142
Table 4-8
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
DI: Digital input; DI/DO: Bidirectional digital input/output; M: Electronics ground;
1)
M1: Ground reference
B = Bidirectional; I = Input; GND = Reference potential (ground)
2)
Table 4-9
Pin
1
2
3
4
5
6
7
8
9
SIMOTION D4x5-2
Manual, 04/2014
Digital inputs/outputs X122
Designation
Signal type
1)
2)
DI 0
I
DI 1
I
DI 2
I
DI 3
I
DI 16
I
DI 17
I
M1
GND
M
GND
DI/DO 8
B
DI/DO 9
B
M
GND
DI/DO10
B
DI/DO 11
B
M
GND
Digital inputs/outputs X132
Designation
Signal type
1)
2)
DI 4
I
DI5
I
DI 6
I
DI 7
I
DI 20
I
DI 21
I
M2
GND
M
GND
DI/DO 12
B
Notes
Digital input 0
Digital input 1
Digital input 2
Digital input 3
Digital input 16
Digital input 17
Ground for DI 0 – DI 3, DI 16, DI 17 (electrically isolated relative
to M)
Ground
Digital input/output 8 (can also be used as input for measuring
input or as input for the external zero mark)
Digital input/output 9 (can also be used as input for measuring
input or as input for the external zero mark)
Ground
Digital input/output 10 (can also be used as input for measuring
input or as input for the external zero mark)
Digital input/output 11 (can also be used as input for measuring
input or as input for the external zero mark)
Ground
Notes
Digital input 4
Digital input 5
Digital input 6
Digital input 7
Digital input 20
Digital input 21
Ground for DI 4 – DI 7, DI 20, DI 21 (electrically isolated relative
to M)
Ground
Digital input/output 12 (can also be used as input for measuring
input or as input for the external zero mark)
Interfaces
4.4 Digital I/Os
61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion d435-2Simotion d445-2Simotion d455-2

Table of Contents