Installation
Mounting Brackets
DIN Track
End Plates
Mounting with Screws
4-1-4
Connecting Expansion I/O Units and Expansion Units
Connection Methods
1,2,3...
60
Secure the DIN Track to the control panel using M4 screws at interval of
210 mm or less (6 holes or fewer). The tightening torque is 1.2 N·m.
PFP-100N2
4.5
25
15
25
10
1000
PFP-100N/50N
4.5
15
25
25
10
1000 (500)*
Use the PFP-M End Plates to secure the Units so that they do not move
towards one end or the other of the DIN Track.
1. Open mounting holes in the mounting surface according to the dimensions
diagram.
2. Use M4 screws, which fit the holes on the G9SP-series Controller. The
tightening torque is 1.2 N·m.
This section describes how to connect Expansion I/O Units and Expansion
Units.
1. Remove the cover from the G9SP-series Controller's or the Expansion I/O
Unit's expansion connector. Use a flat-head screwdriver to remove the cov-
er from the Expansion I/O Connector.
28-25 × 4.5 long holes
30±0.3
27
24
25
25
15
10
7.3±0.15
35±0.3
25
25
15(5)*
10
*PFP-50N dimensions are given in parentheses.
Expansion Connector Cover
(1) Remove
Section 4-1
16
29.2
1
1.5
27±0.15
1