Installation; Installation Location - Omron G9SP-N20S Operation Manuals

G9sp series g9sp-n series safety controller
Hide thumbs Also See for G9SP-N20S:
Table of Contents

Advertisement

Installation

4-1
Installation
4-1-1

Installation Location

Installation Environment
Installation in Control Panels
Installation Orientation
56
This section provides precautions on the environmental factors that must be
considered and the installation location of each G9SP-series Unit.
Do not install the G9SP-series Controller in the following locations.
• Locations subject to ambient temperatures lower than 0°C or higher than
55°C.
• Locations subject to condensation as the result of severe changes in tem-
perature.
• Locations subject to ambient humidity lower than 10% or higher than
90%.
• Locations subject to corrosive or flammable gases.
• Locations subject to excessive dust, salt, or metal filings.
• Locations subject to direct shock or vibration.
• Locations subject to direct sunlight.
• Locations subject to water, oil, or chemicals.
Always enclose or protect the G9SP-series Controller sufficiently in the follow-
ing locations.
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power lines.
When the G9SP-series Controller is being installed in a control panel, be sure
to provide proper ambient conditions as well as access for operation and
maintenance.
When installing the G9SP-series Controller in a control panel, it must be
installed with the side with indicators and communications ports facing the
front to ensure proper heat dissipation.
Section 4-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

G9sp-n10dG9sp-n10sG9sp series

Table of Contents