Ethernet Communications
Sample Ladder Programming
(4)
Step
1
The fixed portion of the send command is set. This processing is performed once at startup.
2
Set the control data of the CMND instruction.
3
Clear the receive area in preparation for the first reception.
4
Once the data has been stored in the cleared receive area, check the size, and then start receive processing.
5
From the response, copy the G9SP Communications Transmission Data to CIO 200 and CIO 201 and the G9SP
Safety Input Terminal Data to CIO 202 to CIO 204.
6
Once receive processing has been completed, set G9SP Communications Reception Data to the send com-
mand from CIO 100.
7
Clear the receive area in preparation for the next reception.
8
The send command is sent to the Ethernet send port, which enables sending to the G9SP-series Controller.
130
Initialization
Reception processing
Send processing
Description
Section 7-3
(1)
(2)
(3)
(5)
(6)
(7)
(8)