Omron G9SP-N20S Operation Manuals page 191

G9sp series g9sp-n series safety controller
Hide thumbs Also See for G9SP-N20S:
Table of Contents

Advertisement

Restoring Data to G9SP-series Controller
Procedure
1,2,3...
1. Turn OFF the power supply to the G9SP-series Controller, and then insert
the Memory Cassette.
2. Turn OFF DIP switch pin 4 on the front of the G9SP-series Controller, and
then turn ON the power supply to the G9SP-series Controller.
The system will start in restore standby status at step 3 if the configuration
data stored in the Memory Cassette does not match the configuration data
stored in the G9SP-series Controller.
3. After startup, the ID of the configuration data on the Memory Cassette will
light sequentially on the Safety Input terminal indicators of the G9SP-se-
ries Controller.
MEMORY
4. Once the display configuration ID has been verified and it is confirmed that
the intended configuration data has been stored in the Memory Cassette,
press the Push Switch on the front of the G9SP-series Controller for at
least 1 s to start restoring data. During the restore operation, the Safety In-
put terminal indicators will be sequentially lit from left to right in yellow.
MEMORY
Push Switch
5. Once the restore operation has been completed, the G9SP-series Control-
ler will restart and operate in RUN Mode with the configuration locked.
MS
MEMORY
MC
MS
Not lit
Flashing yellow (0.5-s intervals)
MC
IN LED 0
1 2
3 4 5 6
7 8
The configuration I/O of the configuration data
stored in the Memory Cassette is displayed.
The I/O indicators will light yellow one at a time.
They will light for the four digits of the ID.
MS
Not lit
MC
Flashing yellow (0.25-s intervals)
IN LED 0 1 2 3 4
5 6 7 8 9
The indicators will light from left to right.
Lit green
LOCK
Lit yellow
Not lit
Section 11-3
Waiting for restore
9
Restoring data
Restore operation
completed.
165

Advertisement

Table of Contents
loading

This manual is also suitable for:

G9sp-n10dG9sp-n10sG9sp series

Table of Contents