Ethernet Communications
7-3-2

Application Example

System Configuration
G9SP-series Controller Settings
126
This section uses the following example to describe how to access the G9SP-
series Controller from a Standard PLC by performing Ethernet communica-
tions through an Ethernet Communications Board (CP1W-CIF41).
OMRON Standard PLC (See note.)
CJ1M
CJ1W-ETN21
Ethernet Unit
Switching hub
192.168.250.2
Note This example uses the following OMRON Standard PLC.
Product
CPU Unit (Standard PLC)
Ethernet Communications Unit
Switching hub
Support Software (for setup and
creating ladder programs)
Make the settings for TCP/IP in the system settings of the G9SP Configurator.
These settings are set in the G9SP-series Controller and Ethernet Option
Board when the configuration data is downloaded.
Parameter
IP address
IP address of Ethernet Option Board.
Default value: 192.168.250.1
Subnet mask
Subnet mask of Ethernet Option Board.
Default value: 255.255.255.0
Default gateway
Set the IP address of the default gate-
way. Default value: 0.0.0.0 (IP routing
not supported)
FINS node address
Set the FINS node address of the
Ethernet Option Board. If automatic
setting is specified, a value that
matches the rightmost byte of the IP
address is stored.
Default value: Automatic (matching the
rightmost byte of the IP address)
Setting range: 1 to 254
FINS/UDP
192.168.250.1
G9SP-series Controller
CP1W-CIF41
Option Board
Model/version
CJ1M-CPU11
CJ1W-ETN21
W4S1-05B
CX-Programmer Ver. 9.10
Description
Section 7-3
Set value for this
example
192.168.250.2
No change is
required.
No change is
required.
No change is
required.