Special Adjustments
Analog output 1
Analog output 1
Amplification
CP.29 defines the function of analog output 1.
Value
Function
0
Absolute actual frequency (CP.1)
1
Absolute set frequency (CP.2)
2
Actual frequency (CP.1)
3
Set frequency (CP.2)
4
Output voltage (CP.9)
5
Actual DC voltage (CP.7)
6
Phase current (CP.4)
7
Active current
8
Digital
9
External PID output
10
Absolute external PID output
11
Absolute active current
12
Power module temperature
13
Motor temperature {F5G}
14
Reserved{F5M}
15
Reserved{F5M}
16
Reserved{F5M}
17
Reserved{F5M}
18
Reserved{F5M}
19
Reference frequency {F5G}
20
Absolute reference frequency {F5G}
Adjustment range:
Resolution:
Factory setting:
Note:
With the amplification (gain), the output voltage of the analog output can
be tuned with respect to the signal. An amplification of 1 corresponds to
±100 % = ±10 V.
Adjustment range:
Resolution:
Factory setting:
out
100%
-100%
-100%
Enter-Parameter
-20.00...20.00
10V
Adjustment example :
The analog output shall give +10 V at 70
Hz instead of at 100 Hz: CP.30 = 1.43
CP.30
in
100%
100Hz= 100%
100Hz= 100%
±100Hz= 100%
±100Hz= 100%
500V= 100%
1000V= 100%
2 x rated current= 100%
± 2 x rated current= 100%
±100Hz= 100%
±100Hz= 100%
100Hz= 100%
2 x rated current= 100%
100 °C= 100%
150 °C= 100%
±140Hz= 100%
140Hz= 100%
0...20
1
2
0.01
1.00
100 Hz
CP.30 = -––––– = 1.43
70 Hz
31