Special Adjustments
DC-braking Mode
DC-braking Time
During DC-braking, the motor is not decelerated by a controlled ramp. Quick
braking without regen voltage can be achieved by applying a DC voltage
to the motor winding. Parameter values listed below, determine how the
DC-braking is triggered.
Value DC-Braking Activation
0
Deactivated
1
Activates when direction signal is removed and the output frequency
has reached 0Hz. The braking time is dependent on CP.23 or until
the next direction of rotation.
2*
Activates as soon as the direction signal is removed.
3*
Activates as soon as the direction signal is removed or
changed.
4*
Activates as soon as the direction signal is removed and if the
real frequency goes below 4 Hz.
5*
Activates when the real frequency goes below 4 Hz.
6*
Activates as soon as the set value goes below 4 Hz.
7*
Activates when input I4(terminal 13) is switched.
8
Activates as long as input I4 is switched.
9
Activates before the acceleration ramp when a direction signal is
given. The time is dependent on CP.23.
* Braking time depends on the actual frequency.
Adjustment range:
Resolution:
Factory setting:
Note:
If the braking time depends on the actual frequency (CP.22 = 2...7), it is
calculated as follows:
CP.23 x f
t
=
–––––––––
Brake
100 Hz
Otherwise the braking time corresponds to CP.23.
Adjustment range:
Resolution:
Factory setting:
0...9
Enter-Parameter
real
0.00...100.00 s
0.01 s
10.00 s
1
7
f
100 Hz
f
actual
t
CP.23
Brake
t
27