KEB COMBIVERT F5 series Installation Manual & Operation Manual page 30

1/2 - 1hp 230v
Hide thumbs Also See for COMBIVERT F5 series:
Table of Contents

Advertisement

Special Adjustments
Response to
external overtem-
perature
30
This parameter determines the response of the drive to the external tem-
perature monitoring circuit. In order to activate this function the power circuit
terminals T1, T2 must be connected in accordance with the instruction
manual, see page 14. After that the response can be adjusted according
to following table:
Factory setting = off
If overheat no longer exists, the message E.ndOH (or A.ndOH) is displayed.
Only then can the error be reset or the automatic restart initiated.
CP.28 Display Response
0
E.dOH Immediate disabling of modulation
1*
A.dOH
Quick stop, disabling
modulation after reaching speed 0
2*
A.dOH
Quick stop, holding torque at
speed 0
3
A.dOH
Immediate disabling of modulation
4*
A.dOH
Quick stop, disabling
modulation after reaching speed 0
5*
A.dOH
Quick stopping, holding torque at
speed 0
6*
none
No effect on the drive;
With CP.31, 32=9 an external module
can be controlled (e.g. fan)
7
none
No effect on the drive;
External temperature monitoring
(T1, T2) is not activated!
*)
If the motor is still too hot after 10 seconds, the error E.dOH is triggered
and the modulation is switched off!
Adjustment range:
Resolution:
Setting range:
Restart
Remove fault;
Activate reset
input.
Automatic reset,
if the fault is no
longer present
- No reset
allowed -
0...7
1
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents