Allen-Bradley PanelView 800 2711R-T4T User Manual page 55

Panelview 800 series hmi terminals
Table of Contents

Advertisement

The terminal also secures itself when idle. If terminal input is not received within
the idle timeout period, the user is logged out. The user must log in again to
access the terminal. The default terminal idle timeout is 30 minutes.
Store your password in a safe place. If you forget the password,
IMPORTANT
you will not be able to connect to the PanelView Explorer Startup
window.
Follow these steps to secure the PanelView Explorer Startup window.
1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the Terminal Security tab.
4. Check Terminal Security Enabled.
5. Optionally, enter a new Terminal User Name.
6. Click the Reset Terminal User Password button.
7. In the Reset Password dialog, enter a new password, confirm the password,
then click OK.
TIP
Rockwell Automation Publication 2711R-UM001E-EN-E - January 2017
Terminal user names are limited to 15 characters.
Configuration Mode
Chapter 2
55