Chapter 8
Troubleshoot the System
PanelView 800 Terminal Alerts
Category
ID
Communication
27
Communication
28
Communication
30
Recipe
1001 Recipe upload started.
Recipe
1002 Recipe save failed. Cause: Recipe in Table has not
Recipe
1003 Recipe save had errors.
Recipe
1004 Recipe save completed successfully.
Recipe
1005 Recipe download failed. Cause: Operation
Recipe
1006 Recipe download started.
Recipe
1007 Recipe download completed with errors.
Recipe
1008 Recipe download completed successfully.
102
Description
Remote Device /*S:0 Param1*/ is Not
Responding
Invalid Data Address /*S:0 Param1*/
Bad address in block /*S:0 Param1*/ to /*S:0
Param2*/ on device /*S:0 Param3*/
been modified.
cancelled.
Rockwell Automation Publication 2711R-UM001E-EN-E - January 2017
Corrective Action
Verify all network connections are correct.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
Verify that the network address of the controller
matches the terminal controller address configured
in the Communication tab.
In the Communication tab, verify that the protocol
specifications are correct, such as communication
rate, data bits, stop bits. These are all protocol
specific.
This is not syntactically a valid address.
This can occur when a write only address for a
controller has been set for read/write in the external
tag of the terminal. Param1 to Param2 specifies the
address block having the issue. Somewhere within
the range is where the write only address is defined
in a PanelView external tag. Set the external tag to
write.
This message is for informational purposes. No
corrective action needed.
Make sure that the recipe table is modified before
the save operation is done.
This message is for informational purposes. No
corrective action needed.
This message is for informational purposes. No
corrective action needed.
This message is for informational purposes. No
corrective action needed.
This message is for informational purposes. No
corrective action needed.
This message is for informational purposes. No
corrective action needed.
This message is for informational purposes. No
corrective action needed.