Chapter 8
Troubleshoot the System
PanelView 800 Terminal Alerts
Category
ID
Alert
2068 Only one Trend with data logging is allow
Alert
2069 Landscape Orientation. Confirm Restart?
Alert
2070 Portrait Orientation. Confirm Restart?
Alert
2071 Application was designed for a different
Alert
2072 Application was designed for a different Platform
Alert
2073 Non-validated application is not supported for
Alert
2074 Terminal encountered an exception and will
Alert
2075 Application will be unloaded. Confirm (Y/N)?
Alert
2076 This application does not have at least one Goto
Alert
2077 Controller Settings cannot be changed for running
Alert
2078 Controller address cannot conflict with PV800
Alert
2079 CompactLogix controller based application must
Alert
2080 Invalid View-Only password. Password should not
Alert
2081 Old password does not match with terminal.
Alert
2082 VNC Server error.
Alert
2083 Controller address cannot be larger than PV800
Alert
2084 Password cannot be empty.
Alert
2085 Enable Ethernet port. Confirm Restart?
Alert
2086 Disable Ethernet port. Confirm Restart?
Alert
2087 Enable Serial port. Confirm Restart?
Alert
2088 Disable Serial port. Confirm Restart?
Alert
2089 Cannot disable both communication port.
108
Description
Orientation and may not appear or operate as
intended. Continue?
type and Orientation, and may not appear or
operate as intended. Continue?
CompactLogix controller. Please validate before
loading
reboot
Config button. Set as Startup Application?
application.
Station Address.
contain valid path.
contain any special character.
Max Node('31').
Rockwell Automation Publication 2711R-UM001E-EN-E - January 2017
Corrective Action
Make sure the application only has one Trend with
data logging.
Select No to restart later.
Select No to restart later.
Press Yes to continue, or No to cancel. Then change
the orientation of the application in Connected
Components Workbench software to match the
terminal and try again.
Press Yes to continue, or No to cancel. Then change
the catalog of the application in Connected
Components Workbench software to match the
terminal and try again.
Validate the application and correct any validation
errors, save the application, then try again.
This message is for informational purposes. No
corrective action needed.
Press Yes to unload the application.
Press Yes to continue setting the application as a
startup application, or No to cancel. Edit the
application and make sure there is at least one Goto
Config button.
Stop the application and try again.
Make sure the controller address is different from
the PanelView terminal 800 station address.
Make sure a valid path exists and try again.
Make sure the View-Only password does not
contain any special characters.
Make sure the correct password is entered in the
Old Password field.
Restart the terminal and try again.
Make sure the address of the controller is smaller
than the maximum node of PanelView 800 ('31').
Please enter valid password.
Press Yes to restart the terminal.
Press Yes to restart the terminal.
Press Yes to restart the terminal.
Press Yes to restart the terminal.
Make sure at least one communication port is
enabled.