242 Safe torque off function
Single-channel connection
ACS880-07
ZCU
Notes:
• Both STO inputs (IN1, IN2) must be connected to the activation switch. Otherwise, no SIL/PL
classification is given.
• Pay special attention to avoiding any potential failure modes for the wiring. For example, use shielded
cable. For measures for fault exclusion of wiring, see eg. EN ISO 13849-2:2012, table D.4.
OUT1
+24 V
SGND
IN1
IN2
K