100 Electrical installation
Motor and motor cable
WARNING! Obey the instructions in chapter
them, injury or death, or damage to the equipment can occur.
1. Stop the drive and do the steps in section
18
before you start the work.
2. Check that the motor cable is disconnected from the drive output terminals U2, V2 and
W2.
3. Measure the insulation resistance between each phase conductor and then between
each phase conductor and the Protective Earth conductor using a measuring voltage
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
consult the manufacturer's instructions.
Note: Moisture inside the motor casing will reduce the insulation resistance. If
moisture is suspected, dry the motor and repeat the measurement.
ohm
ohm
Custom brake resistor assembly
Check the insulation of the brake resistor assembly (if present) as follows:
WARNING! Obey the instructions in chapter
them, injury or death, or damage to the equipment can occur.
1. Stop the drive and do the steps in section
18
before you start the work.
2. Check that the resistor cable is connected to the resistor, and disconnected from the
drive output terminals R+ and R-.
3. At the drive end, connect the R+ and R- conductors of the resistor cable together.
Measure the insulation resistance between the combined conductors and the PE
conductor by using a measuring voltage of 1 kV DC. The insulation resistance must be
higher than 1 Mohm.
ohm